by Shawn Lee
Next in our heat detector layout series is beam construction. For this post, we will assume that our beamed ceiling is level and the ceiling is 10 feet or less from the finished floor. There are some similarities between heat detector layout on joist ceilings and beamed ceilings with regards to reduced spacing at a right angle to the beams. However, the reduction is a little less. Therefore, we must reduce heat detector spacing by 50% at right angles to the joists — on a beam ceiling our heat detector spacing may have to be reduced to not more than around 66% of the listed spacing at right angles to the beams. This may seem a little confusing because that’s not how NFPA 72 phrases it. We will come back to that in just a bit. Here is what NFPA 72 has to say about heat detector location and spacing for beam ceilings:
- 17.6.3.3.1.1 A ceiling shall be treated as a smooth ceiling if the beams project no more than 4 in. (100 mm) below the ceiling.
- 17.6.3.3.1.2 Where the beams project more than 4 in. (100 mm) below the ceiling, the spacing of spot-type heat detectors at right angles to the direction of beam travel shall be not more than two-thirds of the listed spacing.
- 17.6.3.3.1.3 Where the beams project more than 18 in. (460 mm) below the ceiling and are more than 8 ft (2.4 m) on center, each bay formed by the beams shall be treated as a separate area.
- 17.6.3.3.2 Location. Where beams are less than 12 in. (300 mm) in depth and less than 8 ft (2.4 m) on center, detectors shall be permitted to be installed on the bottom of beams.
Let’s talk about each requirement. The first requirement, 17.6.3.3.1.1, simply tells us that beams that project 4 inches or less from the ceiling are not considered as beams. We treat it no differently than a smooth ceiling. As for where the detectors are mounted, make sure you review 17.6.3.3.2.
The second requirement, 17.6.3.3.1.2, tells us that if our beams do project more than 4 inches from the ceiling, then we must reduce our heat detector spacing at right angles to the beams. That reduced spacing is to be no more than 2/3 or about 66% of the detector’s listed spacing. The reason we say about 66% is because when doing the math, 2/3 of 100% = 66.66666…%. So, depending on whether you choose to round up or round down, you will have a maximum spacing of 66% or 67% of the detector’s listed spacing. That does make a difference in your layout. It is best to be more cautious and use 66%, as using 67% could result in a code violation. Therefore, using 66% or even 66.66666% vs. 67% is recommended. For example, in the case of our heat detector with 30-foot spacing here’s the difference:
- Option #1: S x 0.66
30 x 0.66 = 19.8 feet spacing at right angles to the beam
- Option #2: S x 0.6666666
30 x 0.66 = 19.999998 feet spacing at right angles to the beam
- Option #3: S x 0.67
30 x 0.67 = 20.1 feet spacing at right angles to the beam
30 x 0.66 = 19.8 feet spacing at right angles to the beam
30 x 0.66 = 19.999998 feet spacing at right angles to the beam
30 x 0.67 = 20.1 feet spacing at right angles to the beam
The difference between option #1 and #3 is 0.3 feet or a little less than 4 inches. It may not seem like a lot, but when you have multiple detectors in an area, 4 inches for each detector starts adding up and you will end up with a detector layout that is not code compliant. At the end of this post, there will be more discussion about the 2/3 reduction, but for now, let’s continue.
If you read the post on heat detector layout for solid joist ceilings, there was a brief explanation as to why the heat detector spacing is reduced at right angles to the joists. It has to do with the way heat will travel across the ceiling at right angles to the joists. The same is true of beam ceilings. Although the beams will be placed further apart than the joists, the heat traveling across the ceiling will still be slightly impeded by the beams. The space between the beams will “fill up” with heat before “spilling” into the next beam pocket. This can create a situation in which the detector response is delayed. Placing the heat detectors closer together will help to reduce the amount of time for the detectors to sense the heat and signal an alarm to the control unit.
Our third requirement, 17.6.3.3.1.3 tells us that if the beams project MORE THAN 18 inches from the ceiling AND are spaced MORE THAN 8 feet on center, then each bay formed by the beams is considered a separate area for heat detector layout purposes.
Our last requirement, 17.6.3.3.2, lets us know that if the beams project LESS THAN 12 inches from the ceiling AND are LESS THAN 8 feet on center, then we are permitted to install the heat detectors on the bottom of the beams. Pretty straight forward.
Having read through all of that, you may be wondering how it plays out on a layout. For ceilings that have beams that project 4 inches or less from the ceiling, the spacing and installation is exactly like a smooth ceiling which we covered in another post, therefore there’s no illustration for that. But let’s look at the other requirements.
Example #1:
- Beams project 6 inches from the ceiling.
- Beam spacing is 6-foot centers.
- Ceiling height is 10 feet or less and ceiling is level.

The beams for the illustration above project more than 4 inches from the ceiling, so 17.6.3.3.1.2 is applicable. We must reduce the heat detector’s listed spacing to no more than 66% at right angles to the beams. And you must also recall that a heat detector may not be any further than 1/2 or 50% of its spacing from the sidewall. That means at right angles to the beams, our heat detector spacing can be no more than S x 0.66 ÷ 2 from the sidewalls. In our case, this is 30 x 0.66 ÷ 2 = 9.9 feet. As you can see, in the illustration above, the distance is 9 feet from the sidewalls so the detectors could be mounted on the bottoms of the beams making 17.6.3.3.2 applicable because of the beam depth and spacing. However, I could have also placed the detectors inside a beam pocket, so long as I did not exceed 2/3 spacing (19.8 feet) between them as shown in the illustration below.

In this illustration, notice the detectors are in the beam pockets and moved 3 feet closer to the sidewalls. There is now 18 feet between the heat detectors (still less than 19.8 feet).
Now let’s look at a larger space with larger beams depths and spacing.
Example #2:
- Beams project 20 inches from the ceiling.
- Beam spacing is 15-foot centers.
- Ceiling height is 10 feet or less and ceiling is level.







